Findings (3)
Expand a finding to see its evidence. Verify sources, edit wording, set status/severity, attach photos, or request a firm-voice rewrite — every change saves and the admin reviewer sees it.
Minor(2)
Finding text
One puddle weld absent at composite deck side lap near column D-8. Remaining welds on this panel conform to 12 in. o.c. spacing. Contractor to install and re-inspect.
RewriteEvidence (0)
This finding has no supporting evidence. Attach a photo or verify a source before sign-off, or it will block the report.Finding text
Two observed deck splices measured below the 2 in. minimum lap. Contractor to correct and re-submit for observation.
RewriteEvidence (0)
This finding has no supporting evidence. Attach a photo or verify a source before sign-off, or it will block the report.
Other findings(1)
Finding text
Three shear studs exhibit rust bloom following recent precipitation. Steel fabricator to clean to SSPC-SP2 and apply approved touch-up coating prior to concrete placement.
RewriteEvidence (0)
This finding has no supporting evidence. Attach a photo or verify a source before sign-off, or it will block the report.